ALARM UNIT CONFIGURATION
Follow these steps to configure a CM9760-ALM alarm unit.
NOTE: This programming is required only on the recorder that is physically connected to the CM9760-ALM.
1. Go to Start > Programs > DX9000 Server > IO Handler Configuration. The following dialog box appears.
NOTE: You can also open the I/O Handler from the DX9000 Server Configuration Utility.
Figure 91. Alarm I/O Handler Configuration Dialog Box
2. Click Select Driver on Device 1 (COM 1) or Device 2 (COM 2) to define the external device that is connected to the
recorder. The following dialog box appears.
Figure 92. CM9760 Alarm Driver Dialog Box
3. Select CM9760ALM.dll.